HCP-E(SCI)/SIL
- SIL Level 2 approved
- Ideal for use in oil and gas environments
- Fast response
- Integral short-circuit isolator
- Bi-coloured status LED
- Non-frangible element fitted as standard (conforms to EN54)
- Addressed with TCH-B200 Hand Held Programmer
- Surface or flush mounting (if surface mounting, requires SR MOUNTING BOX – sold separately)
- LPCB Approved to EN54-11
Model HCP-E(SCI)/SIL is a Manual Call Point with integral short-circuit isolator, which has been independently assessed and approved for use in a SIL2, low demand safety function with regards to random failure rates.
The unit incorporates a bi-coloured LED, which can be selected as pulsing/non-pulsing*1 for communications polling and is continuously lit when the HCP-E(SCI)/SIL is operated – in these two states the LED will show red. The LED will show amber when a short-circuit is present but will switch to red if the unit is activated. A built in test function initiated by the control panel ensures the integrity of the device at all times and the device can be tested by insertion of a test key in the underside of the unit. Two terminal blocks are provided for easy connection to the loop wiring.
The unit is addressed using the TCH-B200 Hand Held Programmer for quick and reliable addressing. The unit can be flush mounted as supplied.
For surface fixing a suitable back box such as the SR MOUNTING BOX is required (sold separately).
An optional glass element is also available.
Color | Red |
---|---|
Manufacturer | Hochiki |
Waterproof | NO |
Approvals | En 54-11, En 54-17 |
IP Rate | IP24 |
Analog Protocol | Hochiki Esp |
addressing | Yes |
Intrinsically Safe | No |
Electrical Specifications | 17 - 41 V dc |
Operating Temperature Range | -10°C TO +50°C |
Marine Approved | No |
Isolator | Yes |
Relay | No |
SIL Approved | Yes |
Icon | Label | Description | Type | Size | Download |
---|---|---|---|---|---|
HCP-ESCISIL_Specification | HCP-ESCISIL_Specification | 258.2 KB | Download |